FUENTEPON30
New product
OLT Power Supply, 53.5V and 30A Output for batteries.
Two PSU R4815N 30A module + 4 Power output port, each provide 25A MAX + one PMU 11A management and monitoring module SMU01C.
Compatible with Huawei OLT.
Warning: Last items in stock!
Availability date:
OLT Power Supply, 53.5V 30A
OLT Power Supply, 53.5V and 30A Output for batteries.
Two PSU R4815N 30A module + 4 Power output port, each provide 25A MAX + one PMU 11A management and monitoring module SMU01C.
Compatible with Huawei OLT.
Recipient :
* Required fields
or Cancel
GPON | OLT |
ETP4830-A1 is an AC/DCembedded power system with excellent performance such as high power efficiency, intelligent battery management, remote management, wide range of AC input voltage, etc. The system can configure 2 pieces of 1U 15A high rectifier modules, and provides 30A rated current output. ETP4830-A1 can be embedded in 19-inch rack or cabinet.
Product Type | ETP4830-A1 | |||
System | Dimension | 442 mm (W) ×255 mm (D) ×43.6 mm (1U,H) | ||
Weight | ≤ 8 kg (fully loaded) | |||
Cooling Mode | Natural cooling | |||
Installation Mode | Installed on 19-inch rack or cabinet | |||
Cabling Mode | Front inlet and front outlet | |||
Maintenance Mode | Front | |||
Protection Level | IP20 | |||
Input | AC Input Voltage | 85–300 Vac, rated value: 220 Vac, 220 Vac single-phase or 110 Vac dual-live wire | ||
Input Frequency | 45–66 Hz, rated value: 50/60 Hz | |||
Input Capacity | - | |||
Output | AC Output | - | ||
Output Voltage | 42-58 Vdc, rated value: 53.5 Vdc | |||
Maximum Capacity | 2 kW | |||
Battery Breakers | 1 x 20 A (fuse) | |||
LLVD Breakers | - | |||
BLVD Breakers | 2 x 20 A (fuse) | |||
SPD | - | |||
EMC & Safety | EMC | CISPR 22/EN 55022, IEC 61000-3-2, IEC 61000-3-3, EN61000-4-11 | ||
Safety | IEC/EN60950-1/GB 4943 | |||
Enviroment | Operating Temperature | -40ºC to +70ºC (NOTE: The system can run for 8 hours at 70ºC) | ||
Storage Temperature | -40ºC to + 70ºC | |||
Operating Humidity | 5% - 95% (non-condensing) | |||
Altitude | 0 – 4000 m (When the altitude ranges from 2000 m to 4000m, the operating temperature decreases by 1ºC for each additional 200 m) |
Product Type | R4815G1 | R4815N1 | |
Rectifier | Efficiency | > 95% (60% to 100% load) >96% Max | > 93% (30% to 100% load) |
Maximum Power | 870 W (176 to 300 Vac) | 1000 W (176 to 300 Vac) | |
Input Voltage | 85 to 300 Vac | ||
Working Temperature | -40 ºC to +75 ºC (full output below 65ºC), EST EN 300-019 | -40 ºC to +75 ºC (full output below 55ºC), EST EN 300-019 | |
Dimension | 95.5 mm(W) x 208 mm(D) x 40.8 mm(H) | ||
Weight | ≤1.2 kg | ≤1.1 kg | |
Coolding | Forced Air cooling (Built-in fan) | ||
Power Factor | ≥ 0.98 (> 50% load at 230 Vac) | ≥ 0.98 (> 50% load at 230 Vac), ≥ 0.99 (100% load at 230 Vac) | |
THD | ≤ 5% (> 65% load at 230 Vac) | ≤ 5% (> 50% load at 230 Vac) |
Product Type | SMU01A | SMU01B | SMU01C | |
Controller | Signal Input | 7 digital inputs (need interface Unit MUE02A or MUE02B) | 7 digital inputs (need interface Unit MUE02A or MUE02B), 1 analog input. | 2 digital inputs, 2 analog inputs |
Alarm Output | 8 dry contacts (need interface Unit MUE02A or MUE02B | 4 dry contacts | ||
Communication Port | RS232, RS485, FE | RS232, RS485 | ||
Display Mode | LCD |